Why does it Dump?
The core safety principle of a Reduced Pressure Zone (RPZ) assembly is maintaining a hydraulic buffer. The pressure in the center chamber (Zone 2) must ALWAYS be lower than the supply pressure (Zone 1).
Zone 1 (Supply): 60.0 PSI
Zone 2 (Reduced): 51.8 PSI
-------------------------
Apparent DP: 8.2 PSID
If Check Valve 1 (CV1) fails, high-pressure water bleeds into Zone 2. As the Differential Pressure (DP) drops towards 2.0 PSID, the heavy relief valve spring overcomes the hydraulic pressure holding it shut.
Result: The port opens, expelling the contaminated water and maintaining the physical air gap to protect the city water supply!